Correct Answer - Option 3 : 1900 kVA
Concept:
- A Current Transformer (CT) is used to measure the current of another circuit.
- CTs are used worldwide to monitor high-voltage lines across national power grids.
- A CT is designed to produce an alternating current in its secondary winding that is proportional to the current that it is measuring in its primary.
- In doing so, the current transformer reduces a high voltage current to a lower value and therefore provides a safe way of monitoring electrical current flowing in an AC transmission line.
Calculation:
Given:
CT Primary current, ICT,p = 100 A
CT Secondary current, ICT,s = 5 A
Primary Line voltage of Transformer, VR = 11 KV
Distribution Transformer ⇒ star - star connected
Now,
CT's are single phase, therefore ICT,p = IR
Transformer primary phase current, IR = 100 A
KVA load on distribution transformer = √3 VR IR
= √3 × 11 × 100
≈ 1900 KVA