Refrigerant-134a is compressed steadily by a compressor. The power input to the compressor and the volume flow rate of the refrigerant at the compressor inlet are to be determined.
Assumptions:
- This is a steady-flow process since there is no change with time.
- Kinetic and potential energy changes are negligible.
- The device is adiabatic and thus heat transfer is negligible.
Properties: From the refrigerant tables (Tables A-11 through 13)
Analysis:
(a) There is only one inlet and one exit, and thus \(\overset •m_1 = \overset •m_2 = \overset •m\). We take the compressor as the system, which is a control volume since mass crosses the boundary. The energy balance for this steady-flow system can be expressed in the rate form as
(b) The volume flow rate of the refrigerant at the compressor inlet is
\(\overset • V_1 = \overset •mv_1\)
= (1.2kg/s)(0.17395 m3/kg)
= 0.209 m3/s