One phase of the system is shown in Fig.Impedance per phase of high voltage line = (8 + j 10)

Impedance of the transformer primary
= (7.5 + j 13.2) ohm
Total impedance on the high-tension side
= (8 + j 10) + (7.5 + j 13.2) = 15.5 + j 23.2
This impedance can be transferred to secondary side by using the relation given in Hence, impedance as referred to secondary side is
= (15.5 + j 23.2)/52 = 0.62 + j 0.928
Adding to them the impedance of the transformer secondary, we get the total impedance as referred to low-voltage side
= (0.62 + j 0.928) + (0.35 + j 0.65) = 0.97 + j 1.578
Now, kVA load per phase = 2,000/3.0 = 667
Receiving-end voltage/phase = 6.6/ √3 = 3.81 kV
∴ current in the line = 667/3.81 = 175 A
Drop per conductor = I(R cos φ + X sin φ) = 175(0.97 × 0.8 + 1.578 × 0.6) = 302 V
Now, ES = ER + I(R cos φ + X sin φ)
Hence, sending-end voltage (phase to neutral as referred to the lower voltage side) is 3,810 + 302 = 4,112 V. As referred to high-voltage side, its value = 4,112 × 5 = 20,560 V
Line voltage = 20,560 × √3 /1000 = 35.6 kV
If φS is the power factor angle at the sending-end, then

∴ φS = tan–1(0.796) = 38°31′
∴ cos φS = cos 38°31′ = 0.782
Power loss/phase = 1752 × 0.97/1000 = 29.7 kW
Power at the receiving end/phase = 2000 × 0.8/3 = 533.3 kW
∴ transmission efficiency
